The YBW series of high- and low-voltage prefabricated substations are self-contained, complete switchgear and distribution units designed for AC power systems with a frequency of 50 Hz and voltages ranging from 6 to 10 kV, with rated capacities from 50 to 2,500 kVA. They are suitable for both indoor and outdoor applications in urban high-rise buildings, residential communities, industrial and mining facilities, hotels, hospitals, parks, oilfields, airports, ports, shopping malls, railway stations, and temporary installations.
The YBW series of high- and low-voltage prefabricated substations can be used in both ring-network distribution systems and as terminal power supply for radial grid configurations.
Both the metal-housed enclosure and its internal framework have undergone comprehensive anti-corrosion treatment, ensuring long-term outdoor durability.
The box top features a double-layer all-metal structure with an internal insulation layer and ventilation ducts, effectively mitigating solar heat radiation to achieve thermal insulation, exhaust ventilation, and cooling. Non-metallic materials inherently exhibit excellent resistance to intense sunlight exposure, and users may also opt to install additional insulation layers and ventilation systems upon request.
An automatic venting device is installed at the top of the transformer room, while a perforated plate is laid at the bottom. When the upper-oil temperature of the transformer or the ambient temperature reaches the set threshold, the exhaust fan automatically starts, forcing air convection to remove hot air, thereby reducing the transformer’s temperature rise and increasing its output capacity.
Doors are installed on both sides of the transformer room to facilitate the installation and maintenance of the transformer, and an interlock alarm system is also provided to ensure stable equipment operation.
Technical Specifications
| Name | Unit | High-voltage side | Low-voltage side | Transformer |
| Rated voltage | KV | 10(6,20) | 0.4 | 10 (6, 20) / 0.4 |
| Rated capacity | Kilovolt-ampere | 50-2500 | ||
| Rated current | A | 160-630 | 100-3000 | |
| Rated short-circuit breaking current | KA | 20–31.5–50 | 15;30;50;100 | |
| Rated short-circuit making current | KA | 50 | ||
| Rated thermal stability current | KA/S | 20/2 | ||
| Rated dynamic stability current | KA | 50 | ||
| Power-frequency withstand voltage | KA/min | To ground: 42; Fracture: 48 | 2.5 | Oil 35 / Dry 28 |
| Impulse withstand voltage | KV | To ground: 75; Fracture: 85 | 75 | |
| Enclosure Protection Rating | IP43 | IP43 | IP43 | |
| Noise level | decibel | Oil 55/Dry 65 | ||