Product Description: The MNS low-voltage withdrawable switchgear is a modular, assembled low-voltage withdrawable switchgear system constructed from standardized components. This equipment is suitable for AC power systems with frequencies of 50–60 Hz and rated operating voltages of 660 V or less, and is used for the control of power generation, transmission, distribution, power conversion, and electrical load equipment. It is widely employed in power plants, substations, industrial and mining enterprises, and high-rise buildings as both power distribution centers (PC) and motor control centers (MCC). When equipped with intelligent meters, it can be integrated with a host computer to form an intelligent distribution cabinet and a computer-based monitoring system.
This equipment complies with IEC 439, VDE 60, and the national standard GB 7251.1-2013 “Low-Voltage Switchgear and Control Gear Assemblies,” as well as the industry standard JB/T 9661-1999 “Low-Voltage Withdrawable Switchgear and Control Gear Assemblies” and the national standard GB/T 24274-2009 “Low-Voltage Withdrawable Switchgear and Control Gear Assemblies.”
Product Features: Compared with traditional products, the MNS switchgear offers numerous advantages. It features a compact design, high structural versatility, and flexible assembly; its standard modular architecture allows over 200 types of components to be combined into various cabinet frame configurations and drawer units. The equipment boasts excellent stability and superior technical performance, occupies a smaller footprint, achieves a high degree of standardization, modularity, and serialization, thereby significantly reducing the space required for storing and transporting prefabricated components. Additionally, it is easy to assemble and does not require specialized or complex tools.
Technical specifications:
| Project | Data |
| Rated Insulation Voltage | 660V |
| Rated operating voltage | 380V, 660V |
| Maximum Operating Current of the Main Busbar | 6300A |
| Short-time (1 s) withstand current of the main busbar, Icw | 100 kA (RMS) |
| Short-time peak withstand current of the main busbar, lpk | 250 kA (maximum) |
| Peak withstand current of the distribution busbar (vertical busbar) | 1600A |
| Short-time peak withstand current of the distribution busbar (vertical busbar), lpk | Standard type: 90 kA (maximum); Reinforced type: 130 kA (maximum) |
| Protection rating | IP30 |
| External dimensions (width × depth × height) | 600(800, 1000) × 800 (1000) × 2200 |