HXGN-12 High-Voltage Ring Main Switchgear: This is a box-type, fixed, metal-enclosed high-voltage switchgear designed for indoor use in three-phase AC systems at 50 Hz and 3–12 kV. It is employed in ring-network power supply systems and user substations for the reception, control, and distribution of electrical energy. The switchgear can interrupt and make load currents, close rated short-circuit currents, and also interrupt no-load transformer currents as well as capacitive currents from overhead lines, cables, and shunt capacitors over specified distances. Load switch–fuse combination switchgear can be used for the control and protection of distribution transformers, high-voltage motors, shunt capacitors, and other electrical equipment.
Product Features: The switchgear cabinet is assembled from profiled sections. The upper front portion of the cabinet houses the instrument door and relay compartment, where instruments, indicator lights, and electrically operated changeover switches can be installed. The front panel is equipped with a label indicating the location of the manual operation box, an observation window, a simulated busbar, and a live-indication device. The cabinet features a rational design, an aesthetically pleasing appearance, and an ingress protection rating of IP20.
Technical specifications:
| Project | Unit | Load Switchgear | Combined electrical cabinet | |
| Rated voltage | KV | 12 | 12 | |
| Maximum operating voltage | KV | 12 | 12 | |
| Rated frequency | Hangzhou | 50 | 50 | |
| Rated current | Main bus | A | 630, 1250 | 630 |
| Load switch | A | 630, 1250 | 630 | |
| Maximum rated current of the fuse | KV | 125 | ||
| Rated short-time withstand current (4 s) | KA | 20 | Depends on the fuse. | |
| Rated peak withstand current | KA | 50 | Depends on the fuse. | |
| Rated short-circuit making and breaking current | KA | 50 | Depends on the fuse. | |
| Rated breaking current | Active load current | A | 630, 1250 | 630 |
| Closed-loop current | A | 630, 1250 | 630 | |
| No-load transformer | Kilovolt-ampere | 1600 | ||
| Cable charging current | A | 25 | 25 | |
| Protection rating | IP30 | IP30 | ||
| External dimensions (width × depth × height) | Formal attire | 900*900*2200(2000) | ||
| Side-mounted | 700*900*2200(2000) | |||
keywords: