Product Description: The modular substation for wind power generation is a prefabricated, packaged substation that integrates a step-up transformer, switchgear, fuses, tap changers, and associated auxiliary equipment. Both the high-voltage switchgear and fuses are housed within an oil-filled tank, resulting in a compact overall footprint. Its structural configuration is similar to the pad-mounted substations introduced from the United States in the 1990s, and it is commonly referred to in the industry as “wind-power American-style substation.” Based on product structure and component configuration, it can be classified into two types: one with fully insulated high-voltage outgoing lines, and the other with porcelain bushing-type high-voltage outgoing lines.
Product Application: Prefabricated substations for wind power generation serve as step-up equipment in wind farms and are typically installed in sparsely populated areas such as coastal zones, deserts, and grasslands. Given the extensive footprint of wind farms and the harsh natural conditions in these locations, the step-up equipment is required to exhibit high environmental adaptability. In addition, the airflow passing over the turbine blades and the wake generated by wind energy both produce noise, and the operation of the step-up equipment itself also generates noise. In response to these characteristics of wind power generation, our company has developed a dedicated step-up solution: a prefabricated substation for wind power generation.
Operating environment:
1. Altitude: ≤1000 meters;
2 Ambient temperature: maximum +50°C, minimum -45°C;
3 Maximum wind speed: 70 m/s;
4. Seismic resistance: horizontal acceleration shall not exceed 0.3g, and vertical acceleration shall not exceed 0.15g;
5. Pollution degree: Level III (minimum creepage distance per kV of highest operating voltage not less than 31 mm/kV);
6. The enclosure protection rating is IP54.
Technical Specifications
| Serial Number | Name | Parameters | Remarks | ||
| Input | Output | ||||
| 1 | Rated Voltage (kV) | 0.69 | 10 | 35 | |
| 2 | Rated frequency (Hz) | 50 | |||
| 3 | Rated Capacity (kVA) | 900, 1250, 1600 | |||
| 4 | Rated short-time withstand voltage (kV/1 min) | 42 | 85 | ||
| 5 | System neutral grounding method | Direct grounding | Unearthed | ||
Main Component Parameters
1. Transformer Technical Parameters
| Voltage Combination and Tap Range | Connection Group Symbol | No-load loss (W) | Load Loss (W at 75°C) | No-load current (%) | Short-circuit impedance (%) | |||
| Rated capacity | High Voltage (kV) | High-voltage tap range (%) | Low voltage (kV) | |||||
| 900 | 10 | ±2×2.5% | 0.69 | Dyn11 | 1150 | 10300 | 0.6 | 4.5 |
| 1250 | 1360 | 12000 | 0.5 | 14.5 | ||||
| 35 | ±2×2.5% | |||||||
| 1600 | 1980 | 16230 | 0.45 | 6.5 | ||||
2. Technical Parameters of Fuses
| Serial Number | Name | Unit | Parameters | Remarks |
| 1 | Maximum voltage | KV | 12. 40.5 | |
| 2 | Fuse rated current | A | 40, 50 | |
| 3 | Rated current of the fuse element | A | 20, 25, 31.5, 40, 50 | |
| 4 | Rated Maximum Breaking Current | kA | 50 |
3. Technical Parameters of High-Voltage Load Switch
| Serial Number | Project | Unit | Parameters | Remarks |
| 1 | Rated voltage | KV | 12 | 40.5 |
| 2 | Rated current | A | 630 | 630 |
| 3 | Rated frequency | Hertz | 50 | 50 |
| 4 | Rated short-time withstand current | kA/2s | 12.5 | 20 |
| 5 | Rated peak withstand current | kA | 31.5 | 31.5 |
| 6 | Mechanical life | next time | 2000 | 2000 |
| 1-minute power-frequency withstand voltage (phase-to-phase and phase-to-ground) | KV | 42 | 85 | |
| Lightning impulse level (phase-to-phase and phase-to-ground) | KV | 75 | 185 |
keywords: