Thorough dust removal inside the inverter cabinet is essential to prevent any adverse impact on heat dissipation.
To ensure the reliable and stable operation of high-voltage variable-frequency drives and minimize downtime due to failures, routine operation and maintenance are essential. In particular, after a high-voltage VFD has been shut down or stored for an extended period, it must undergo maintenance and inspection before being put back into service.
To ensure the reliable and stable operation of high-voltage variable-frequency drives and to minimize downtime due to failures, proper daily use and maintenance are essential. In particular, after a high-voltage VFD has been shut down or stored for an extended period, it must undergo thorough maintenance and inspection before being put back into service. During long-term storage, changes in ambient temperature can lead to condensation inside the VFD, resulting in liquid water accumulating on circuit boards, power devices, heat sinks, and other components. This liquid water, often mixed with dust, can cause corrosion of cable connectors, terminals, screws, and other parts, compromising electrical insulation and even creating unintended short circuits that lead to VFD failure. To guarantee the stable operation of high-voltage VFDs, the following measures must be implemented:
Visual inspection:
Before energizing, inspect the VFD for any deformation of its exterior and check whether the cabinet door is warped. Open the cabinet door and examine the interior for signs of moisture, rust, corrosion, arcing, component detachment, or the presence of foreign objects—any abnormal conditions.
Drying and dehumidification treatment:
Drying and dehumidification of the high-voltage variable-frequency drive are carried out using ventilation and heating. An electric-heated drying heater—specifically an industrial-grade unit with a power rating exceeding 3,000 W and equipped with a swiveling hot-air nozzle—is directed at the drive to blow warm air, thereby raising the internal temperature. As the temperature increases, the relative humidity correspondingly decreases. The drying duration is adjusted according to the degree of moisture ingress in the drive; care must be taken during drying to avoid overheating that could damage optical fibers and cables.
When the inverter is only slightly damp, the built-in fan on the inverter cabinet can be used for ventilation and dehumidification. Manually activate the cabinet-top fan to draw fresh outdoor air into the inverter cabinet, equalizing the absolute humidity inside and outside the cabinet and thereby removing moisture from within the inverter. The ventilation period should exceed 8 hours.
Dust removal:
If a variable-frequency drive is left idle for an extended period after operation, failure to promptly remove accumulated dust can impair heat dissipation of the internal components, potentially leading to component damage over time. Before resuming operation, it is essential to thoroughly clean all dust from inside the VFD cabinet. Use a vacuum cleaner to remove dust from both the interior of the cabinet and the surfaces of the individual units. (It is not recommended to use a blower to blow dust off the VFD; if a blower is used, ensure that the dust is expelled outside the VFD cabinet and into the outdoor environment.)
For equipment that has been in operation for more than three months or is located in a harsh on-site environment, the power units should be removed. Each unit should then be taken outdoors and thoroughly cleaned of dust using a blower or compressed air. When dismantling the units, take care to avoid breaking or damaging the optical fibers; during dust-blowing, ensure that the circuit boards and power components are not inadvertently touched. After the dust has been completely removed, tighten all connectors on the unit’s circuit boards and recheck the tightness of the screws on the power components. At the same time, use a multimeter to test the fuses for any damage. While the units are being removed, also clean out the dust inside the power cabinet. For 5000-series models, the unit connectors should be carefully wiped with a cloth lightly moistened with alcohol, and the inverter must be allowed to dry completely before it can be put back into service.