Control cabinet manufacturers should prevent the inadvertent closing of circuit breakers and load switches.
Prevent the operation of isolating switches under load. (Isolating switches shall not be operated when circuit breakers, load switches, or contactors are closed.)
Five-Prevention Functions of High-Voltage Switchgear
The “Five Protections” for electrical systems in control cabinet manufacturers are:
1. Prevent opening or closing the isolating switch under load. (The isolating switch must not be operated when the circuit breaker, load switch, or contactor is closed.)
2. Prevent incorrect tripping or closing of circuit breakers, load switches, and contactors. (Operation on the target equipment is permitted only when the operation command corresponds to the operating device.)
3. Prevent the circuit breaker and load switch from being closed when the earthing switch is in the closed position. (The isolating switch may only be closed, the handcart may only be moved to the working position, and the circuit breaker and load switch may only be operated to close when the earthing switch is in the open position.)
4. Prevent accidental closing of the earthing switch while the system is energized. (The earthing switch may only be closed when the circuit breaker is in the open position, the isolating switch is operated, or the handcart has been withdrawn from the working position to the test position.)
5. Prevent unauthorized entry into energized compartments. (The compartment door may be opened and the compartment entered only when the compartment is de-energized.)
The environmental requirements for the operation of high- and low-voltage control cabinets are as follows:
1. The ambient temperature shall not exceed 40°C, with minimum ambient air temperatures of -5°C, -15°C, and -25°C.
2. Altitude not exceeding 1,000 meters.
3. Temperature: The 24-hour average of the measured temperature and relative humidity shall not exceed 95%; moderate condensation is permissible to accommodate temperature fluctuations.
4. The surrounding air shall not be significantly contaminated by dust, smoke, corrosive or flammable gases, vapors, or salt spray.
These environmental requirements for low- and high-voltage control cabinets also apply to high-voltage variable-frequency drive cabinets, as well as to complete sets of low- and high-voltage equipment housed in enclosures and cabinets. A low- and high-voltage control cabinet is an electrical device that integrates protective components such as switches and circuit breakers into a single unit.
Altitude not exceeding 1,000 meters.
Temperature: The 24-hour average of measured and relative temperatures shall not exceed 95%; moderate condensation is permissible to account for temperature fluctuations.
The surrounding air is not noticeably contaminated by dust, smoke, corrosive or flammable gases, vapors, or salt spray.
These environmental requirements for low- and high-voltage control cabinets also apply to high-voltage variable-frequency drive cabinets, as well as to complete sets of low- and high-voltage equipment housed in enclosures and cabinets. A low- and high-voltage control cabinet is an electrical device that integrates protective components such as switches and circuit breakers into a single unit.