Operating Procedures for High-Voltage Variable Frequency Drives: Guidance from the Control Cabinet Manufacturer
Inspect the three indicator lights on the control interface of the VFD unit cabinet: “High-Voltage Indicator,” “Run Indicator,” and “Fault Indicator.” At this time, all three lights should be off.
I. Preparations Before Power-Up When Commissioning the Variable Frequency Drive
1. Check the three indicator lights on the control panel of the VFD unit cabinet: “High-Voltage Indicator,” “Running Indicator,” and “Fault Indicator.” At this time, all three lights should be off. If a major fault occurs (the Fault Indicator remains steadily lit), simply press the reset button next to the high-voltage disconnect button.
2. Verify that the “High-Voltage Disconnect” button at the bottom of the VFD unit cabinet’s control interface is in the released (unpressed) position.
3. Inspect the control interface on the VFD unit cabinet; the display should indicate “High Voltage Not Ready” with no other fault messages shown. Under these conditions, high voltage can be applied.
4. The manual bypass cabinet is equipped with three indicator lights at the top: “Power Supply Indicator,” “Variable Frequency Operation Indicator,” and “Bypass Operation Indicator.” The Power Supply Indicator signifies the control power status; it illuminates when the control power is on. When both isolating disconnect switches are in the open (up) position, the Variable Frequency Operation Indicator illuminates, indicating variable-frequency operation. When both isolating disconnect switches are in the closed (down) position, the Bypass Operation Indicator illuminates, indicating bypass operation.
II. High Voltage on the Inverter: Operation and Shutdown
1. After completing the above inspection steps, all three indicator lights on the VFD cabinet are off, while the “Power Supply” and “VFD Enabled” lights on the bypass cabinet are on, indicating that high-voltage power can now be applied.
2. Variable-frequency operation: Once the “High-Voltage Indicator” light on the VFD illuminates and the monitor displays “System Standby,” the central control room sets the required frequency for the operating condition, which then drives the VFD. Upon activation of the run indicator light, the load begins to operate.
3. Variable-frequency drive shutdown: To stop the VFD, the central control cabinet disconnects the VFD’s drive signal, causing the VFD to cease output and the running indicator light to turn off.
4. De-energize under high voltage: Disconnect the power supply to the high-voltage switchgear.
3. Bypass Operation
With the high-voltage switchgear in the open position, set both isolating switches on the bypass cabinet to the “down” position. At this point, the “Bypass Enabled” indicator light will illuminate, after which the equipment can be started using the original startup procedure.
IV. Precautions
1. During normal operation of the variable-frequency drive, the top-mounted fan must never be disconnected; otherwise, the drive will trip due to overheating.
2. During operation of the variable frequency drive, unauthorized personnel are strictly prohibited from opening the VFD output terminal compartment or the VFD cabinet doors.
3. During the high-voltage energization of the variable frequency drive, it is strictly prohibited to disconnect the AC 220 V or 380 V supply to the drive.
4. The high-voltage disconnect button on the cabinet door must never be pressed during variable-frequency operation (except in special circumstances).
5. When a fault occurs in the variable frequency drive, an alarm will be triggered. The fault indicator on the VFD has two states: first, a minor fault, indicated by the fault light flashing; this condition does not affect the operation of the VFD and cannot be resolved by resetting it—simply check that the cabinet door is securely closed and verify the transformer temperature. Second, a major fault, indicated by the fault light being steadily on; this signifies a serious fault in the VFD. If the fault cannot be cleared by resetting, contact the manufacturer and provide a detailed description of the fault symptoms.
6. When illuminating the display, press the “SET” key; absolutely no other keys are to be pressed.
7. Regularly monitor the transformer temperature and the temperature inside the variable-frequency drive cabinet. The transformer temperature should be kept below 100°C, and the cabinet temperature below 50°C. If the temperatures exceed these limits, open the doors and use fans to enhance cooling.
8. After high-voltage power is applied, if the electromagnetic lock automatically loses power, operation is prohibited; the key-operated handle must never be used.