Secondary Circuit of the Variable-Frequency Control Cabinet Ensures Safe Operation
In the power system of a variable-frequency control cabinet, the secondary circuit plays a crucial role in ensuring the safe operation of the system.
In the power system of a variable-frequency control cabinet, the secondary circuit plays a crucial role in ensuring the safe operation of the system. Under normal operating conditions, to safeguard both personnel and equipment, the Code for Safety on Electric Power Work stipulates that one electrical connection in the current transformer’s secondary circuit must have a reliable grounding point. At the same time, to ensure the proper functioning of relay protection and automatic devices, the current circuit is required to be grounded at only one point. However, substation current secondary circuits involve numerous connected devices and extensive wiring spans; as a result, due to human wiring errors or unavoidable natural factors such as insulation aging, multiple grounding points often occur within a single electrical connection in the secondary circuit. Moreover, since most of the system’s secondary circuits are located outdoors, the likelihood of insulation failure is high. Such multi-point grounding can lead to incorrect operation of protective devices, frequently causing large-scale power outages. The causes of two-point grounding include the following:
(1) The control panel and the protection panel in the main control room are grounded separately, resulting in two-point grounding.
(2) At the factory, the secondary current circuit grounding point of the 10 kV switchgear was already connected to the circuit breaker enclosure. During installation, the switchgear was connected to the grounding grid, establishing a single-point ground; additionally, a separate grounding connection was made in the control room, resulting in double grounding of the current circuit.
(3) During the substation renovation, the grounding point was relocated to the control room and the grounding connection of the outdoor terminal box was disconnected; however, due to human oversight, a two-point ground fault occurred in the current circuit.
(4) Insulation failure and grounding in the secondary current circuit, resulting in two-point grounding of the current circuit.
Hazards of Two-Point Grounding
(1) The secondary current circuit is connected via cables. When a short-circuit current or lightning current flows through the grounding grid, the potential difference between the two ends of the cable shield causes current to flow within the shield, which may result in its burnout. Once current flows in the shield, it generates interference signals on each core conductor.
(2) In the secondary current circuit, if grounding points happen to exist on both sides of the relay’s current coil, the parallel circuit formed by these two grounding points and earth will short-circuit the current coil, thereby significantly reducing the current flowing through it. Moreover, during a ground fault, the potential difference between the two grounding points—caused by zero-sequence current flowing through the grounding grid—will induce a substantial additional current in the current coil. These two factors will result in a significant discrepancy between the current flowing through the relay’s current coil and the fault current injected at the CT secondary, leading to maloperation of the protection scheme and inaccurate metering.