Condensation may occur in high-voltage variable-frequency drives when the ambient temperature changes.


Control cabinets are used in both indoor and outdoor applications for power and lighting distribution as well as motor control, and are suitable for wall-mounted installation indoors or floor-mounted installation outdoors.

Control cabinets are used in both indoor and outdoor applications for power and lighting distribution as well as motor control, and are suitable for wall-mounted installation indoors or floor-mounted installation outdoors. They are primarily employed for controlling fire pumps, submersible pumps, fire-fighting fans, general ventilation fans, and lighting distribution systems. Control methods include direct-on-line starting, star–delta reduced-voltage starting, autotransformer reduced-voltage starting, variable-frequency drive (VFD) starting, soft-starting, and other configurations. Additionally, isolating switches or fuse-switch combinations may be used as isolation disconnect points.
To ensure the reliable and stable operation of high-voltage variable-frequency drives and to minimize downtime due to failures, routine operation and maintenance of the VFD control cabinet are of paramount importance. In particular, after a high-voltage VFD has been shut down or stored for an extended period, it must undergo thorough maintenance and inspection before being put back into service. Prolonged storage under varying ambient temperatures can lead to condensation inside the VFD, resulting in liquid water accumulating on circuit boards, power components, heat sinks, and other internal parts. This liquid, often mixed with dust, can cause corrosion of cable connectors, terminals, screws, and other components, compromising electrical insulation and even creating unintended conductive paths that may trigger equipment failure. To guarantee the stable operation of high-voltage VFDs, the following measures must be implemented:
Visual inspection:
Before energizing, inspect the VFD for any deformation of its exterior and check whether the cabinet doors are warped. Open the cabinet doors and examine the interior for signs of moisture, rust, corrosion, arcing, component detachment, or the presence of foreign objects—any abnormal conditions.
Drying and dehumidification treatment:
Drying and dehumidification of the high-voltage variable-frequency drive are carried out using ventilation and heating. An electric-heated drying heater—specifically an industrial-grade unit with a power rating exceeding 3,000 W and equipped with a swiveling hot-air nozzle—is directed at the drive to blow warm air, thereby raising the internal temperature. As the temperature increases, the relative humidity correspondingly decreases. The drying duration is adjusted according to the degree of moisture ingress in the drive; care must be taken during drying to avoid overheating that could damage optical fibers and cables.
When the inverter is only slightly damp, the built-in fan on the inverter cabinet can be used for ventilation and dehumidification. Manually activate the cabinet-top fan to draw fresh outdoor air into the inverter cabinet, equalizing the absolute humidity inside and outside the cabinet and thereby removing moisture from within the inverter. The ventilation period should exceed 8 hours.
Dust removal:
If a variable-frequency drive is left idle for an extended period after operation, failure to promptly remove accumulated dust can impair heat dissipation of the internal components, potentially leading to component damage over time. Before resuming operation, it is essential to thoroughly clean all dust from inside the VFD cabinet. Use a vacuum cleaner to remove dust from both the interior of the cabinet and the surfaces of the individual units; however, using a blower to blow dust out of the VFD is not recommended, as this method may displace dust into the cabinet and even outdoors.