The control cabinet busbar uses high-quality, high-conductivity, high-current-carrying-capacity busbars.


The operation of distribution cabinets (boxes) must be carried out by designated personnel who have undergone training and obtained certification. Operators must be familiar with the location and control range of the main power switch at the workplace, as well as the locations of the branch switches they use.

Operation of distribution cabinets (boxes) shall be conducted by designated personnel who have undergone training and been certified as qualified. Operators must be familiar with the location and control range of the main power switch at the work site, as well as the locations of the branch switches they use. For manual operation: after closing the circuit breaker, set the rotary switch on the exterior of the low-voltage main cabinet to the “Manual” position, then press the green “Start” button to initiate motor operation. To stop the motor, press the red “Stop” button, which will halt its operation. For automatic operation of the low-voltage main cabinet: when the rotary switch on the exterior of the cabinet is set to the “Automatic” position, the motor’s start/stop functions are controlled automatically. Note: Unless otherwise specified, the rotary switch should always be in the “Automatic” position.
If any abnormal conditions are detected in the low-voltage control cabinet, immediately disconnect the power supply; if necessary, also switch off the main power supply.
During operation, ensure adequate ventilation and heat dissipation for the distribution cabinet and motor to prevent overheating that could damage the cabinet or motor.
If any abnormal noises or unusual odors are detected in the distribution cabinet or generator set, immediately disconnect power and perform maintenance.
When performing maintenance on equipment, a “Person at Work—Do Not Close Switch” warning sign must first be hung on the control switch inside the equipment’s distribution cabinet (box).
Preparations:
A. Notify residents of the scheduled power outage and its duration the day before maintenance is performed on the distribution cabinet.
B. Complete all preparatory work before the power outage, ensuring that all necessary tools are fully available; and carry out the maintenance work in the shortest possible outage duration.
Maintenance Procedure:
A. Implement phased maintenance, starting with the security load section.
B. De-energize the emergency load; continue to supply the remaining loads with utility power. Open the circuit breaker supplying utility power to the emergency load, open the generator’s circuit breaker, set the generator selector switch to the “Off” position, and disconnect the positive and negative battery terminals, affixing warning signs to prevent the generator from generating power.
C. Inspect the busbar joints for deformation and any signs of discharge-induced blackening; tighten the connecting bolts, and replace any that are rusted to ensure a secure connection. Also inspect the busbar insulation for looseness or damage.
D. Use the handle to manually operate the main air switch out of the distribution cabinet, inspect the main contacts for signs of burnout or fusion, check the arc-extinguishing cover for blackening and damage, tighten all wiring screws, clean dust inside the cabinet, and test the mechanical closing and opening operations.
E. Remove each branch switchgear cabinet from the drawer-type cabinet and tighten all wiring terminals. Inspect the installation and wiring of current transformers, ammeters, and energy meters; verify the flexibility and reliability of the handle-operated mechanism; tighten the incoming and outgoing leads of the air circuit breakers; and clean dust from inside the switchgear cabinet and at the cable exit points on the rear of the distribution cabinet.
Qualified cabinet bodies shall have sufficient strength and stiffness, with reinforcing ribs provided on the cabinet doors. For wall-mounted, exposed installations, the installation requirements for such configurations must be met, and reinforcement must be applied at the mounting holes; for floor-standing installations, a base shall be provided, fabricated by welding 10-channel steel.
The door opens to an angle greater than 90° and operates smoothly; the door lock features a high-quality lock cylinder with a pop-out function. Sealing gaskets are installed on the door panel to prevent dust and water ingress. A reliable grounding connection shall be provided between the cabinet door and the cabinet body. The upper and lower sides of the enclosure are equipped with removable knock-out holes, which are sealed with covers to prevent dust from entering the cabinet; the placement of these covers does not impede the equipment’s normal ventilation and heat dissipation during operation.
The enclosure is equipped with a mounting base plate for installing electrical equipment. The internal component layout is rational, with clearances that comply with relevant technical requirements, adequate heat dissipation, and sufficient space to accommodate installation, maintenance, and other special operational conditions.
The busbar assembly shall utilize high-quality, high-conductivity, high-current-carrying-capacity busbars that meet the required insulation class and facilitate maintenance.
The selection of components in the control cabinet, including circuit breakers, contactors, and thermal relays, shall be matched to the electrical equipment and shall conform to the drawings; the selected specifications shall not be lower than those indicated on the drawings. Mitsubishi products shall be used for the main components. The wiring terminals shall be flame-retardant and durable, with 20% extra terminals reserved for future expansion. Internal wiring within the cabinet shall be neatly arranged, with standardized numbering; cable identification sleeves shall be printed labels, and equipment tag numbers shall be printed using 3M adhesive labels, all in compliance with relevant standards and as specified in the drawings. The cabinet nameplate shall be made of stainless steel and shall clearly indicate the cabinet serial number, manufacturer, date of manufacture, and other relevant information.