Installation and Principle of Reactive Power Compensation Cabinet


In buildings, with the exception of resistive loads, most electrical equipment is inductive (such as fluorescent lamps, transformers, and electric motors).

  Installation and Principle of Reactive Power Compensation Cabinet

  1. Why is a reactive power compensation cabinet installed?

  In buildings, with the exception of resistive loads, most electrical equipment is inductive (such as fluorescent lamps, transformers, and electric motors). These inductive loads cause a phase shift in the supply voltage—specifically, the current lags behind the voltage—resulting in significant voltage fluctuations, increased reactive power, and substantial energy waste. When the power factor is too low, the resulting excessive supply current can lead to overloading.

  2. Composition and Installation of Capacitor Compensation Cabinets

  Low-voltage switchgear rooms typically consist of three main types of switchgear: incoming feeder cabinets, reactive power compensation cabinets, and outgoing feeder cabinets. Depending on the functional requirements of the building, tie cabinets may also be added, and transformers may be installed within the low-voltage switchgear room.

  The capacitor compensation cabinet is installed behind the incoming feeder cabinet (for centralized compensation in the low-voltage distribution room), and the installation capacity of the capacitor compensation is determined based on the load of the end-use equipment.

  The low-voltage capacitor compensation cabinet consists of a cabinet body, busbars, fuses, isolating switch-fuse units, contactors, surge arresters, capacitors, reactors, primary and secondary wiring, terminal blocks, automatic power-factor correction control equipment, and panel-mounted instruments.

  The installation of the capacitor compensation cabinet is as follows: the incoming busbar is connected to a contactor via an isolating switch and fuses, and the contactor’s output is connected to reactors and capacitors.

  During operation of the reactive power compensation cabinet: the reactive power compensation controller detects the load of the end-user equipment and automatically energizes the required number of capacitor banks via control contactors to provide reactive power compensation, thereby reducing substantial reactive current, minimizing line losses, and delivering a high-quality power supply.

  3. Principle of the Reactive Power Compensation Cabinet

  In power systems, capacitors and reactors are primarily installed in two configurations: series and parallel.

  The function of the series reactor in a reactive power compensation cabinet is to prevent series and parallel resonance between the capacitor and the load system, which could amplify harmonics, leading to overcurrent in the capacitor and subsequent damage.

  Overcurrent Limiting

  The function of shunt reactors in reactive power compensation cabinets is to absorb the charging capacitive reactive power in cable lines; moreover, these reactors can effectively prevent self-excitation resonance from occurring when a generator supplies long transmission lines.

  In civil buildings, inductive loads are prevalent, leading to more significant harmonic distortion; therefore, a reactor should be connected in series at the front end of the capacitor bank.